Description
PRODUCT INFORMATION OF SCHNEIDER LC1D three-level AC contactor LC1D205M7C AC24 220V 380V.
| Product Series of LC1D205M7C | TeSys Deca |
|---|---|
| Product Series | TeSys Deca |
| product type | Contactor |
| product short name | LC1D |
| Application field of contactor | Applied to AC loads with power factor greater than or equal to 0.95 Applied to non-inductive or slightly inductive loads, resistance furnaces |
| use category | AC- 3AC-1 |
| number of poles | 3P |
| Rated working voltage [Ue] | Power circuit: <= 1000 V AC 25…400 Hz Power circuit: <= 460 V DC |
| Rated operating current [Ie] | 275 A 40 °C) at <= 440 V AC AC-1 for power circuits 205 A 40 °C) at <= 440 V AC AC-3 for power circuits |
| [Uc] control circuit voltage | 230V AC 50/60Hz |
| Motor power (kW) | 100 kW at 1000 V AC 50/60 Hz (AC-3) 63 kW at 220/240 V AC 50/60 Hz (AC-3) 110 kW at 380/400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 110 kW at 440 V AC 50/60 Hz (AC-3) 129 kW at 500 V AC 50/60 Hz (AC-3) 129 kW at 660/690 V AC 50/60 Hz (AC-3) |
| model of LC1D205M7C | LC1D |
| Loop contact type | 3 NO |
| protection cap | None |
| Conventional thermal current [Ith] | 275 A at <40 °C for power circuits |
| Rated short-time withstand current [Icw] | 1500 A at <40 °C – 10 s for power circuit 920 A at <40 °C – 30 s for power circuit 740 A at <40 °C – 1 min for power circuit 500 A at <40 °C – 3 minutes for power circuit 400 A at <40 °C – 10 minutes for power circuit |
| Fuses for use with relays | 200 A aM at <= 440 V for power circuits 315 A gG at <= 440 V for power circuits |
| average impedance | 0.33 mΩ – Ith 275 A 50 Hz for power circuits |
| Rated insulation voltage [Ui] | Power circuit: 1000 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| pollution level | 3 |
| Rated impulse withstand voltage [Uimp] | 8 kV according to IEC 60947 |
| Mechanical life | 8 Mcycles |
| Electrical life | 0.55 Mcycles 275 A AC-1 Ue <= 440 V 1.1 Mcycles 170 A AC-3 Ue <= 440 V 1 Mcycles 118 A AC-3 Ue 660/690 V |
| Control loop characteristics | AC at 50/60 Hz |
| Control voltage limit | 0.35…0.55 Uc -5…55 °C release 50/60 Hz 0.85…1.15 Uc -5…55 °C run 50/60 Hz |
| (~50Hz pickup) power consumption (VA) | 805 VA 50 Hz 0.3 20 °C) 970 VA 60 Hz 0.3 20 °C) |
| (~50Hz hold) power consumption (VA) | 55 VA 50 Hz 0.3 20 °C) 66 VA 60 Hz 0.3 20 °C) |
| heat dissipation | 18…24W |
| action time | 20…35 ms close 130 ms break |
| operating frequency | 2400 cycles/h at <55 °C |
| Wiring capacity | Control circuit: Bolt fastening Cable selection: Flexible wire without wire terminal Control circuit: Bolt fastening Cable selection: Flexible wire with wire terminal Power circuit: Bus terminal Cable selection: Hard wire without wire terminal Busbar Cross-section: 25 x 3 mm Power circuit: Cable with lugs Cable selection: single-strand hard wire without wire terminal |
| Tightening torque | Power circuit: 18 Nm Via busbar terminals Power circuit: 18 Nm Via cable connector Control circuit: 1.2 Nm Via bolt fastening |
| Auxiliary contact type | Does not contain |
| installation method | Chassis mounting rail installation |
| standard | GB 14048.4 IEC 60947-4-1 |
| certified product | CCC CE |
| IP protection class | IP20 front panel with LA9F conforming to IEC 60529 |
| Protective measures | TH conforms to IEC 60068-2-30 |
| ambient air temperature | -40…60 °C operation 60…70 °C with derating -60…80 °C storage |
| working altitude | 3000 m None |
| Shock and vibration resistance | Shock resistance with contacts open (2 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance for 11 ms with contacts closed (15 gn) conforming to IEC 60068-2-27 Shock resistance with contacts closed (5 gn (5…300 Hz)) conforming to IEC 60068-2-6 Shock resistance 11 ms contact opening (7 gn) conforming to IEC 60068-2-27 |
| high of LC1D205M7C | 174 mm |
| width of LC1D205M7C | 168.5 mm |
| depth of LC1D205M7C | 181 mm |
| Product Weight | 5.2kg |


0.0 Average Rating Rated (0 Reviews)