Description
PRODUCT INFORMATION OF SCHNEIDER Schneider time relay RE17RCMU
| Range of product | Harmony Timer Relays |
|---|---|
| Product or component type | Single function relay |
| Discrete output type | Relay |
| Width | 17.5 mm |
| Device short name | RE17R |
| Time delay type | Off-delay |
| Time delay range | 6…60 s 1…10 h 1…10 min 6…60 min 0.1…1 s 1…10 s 10…100 h |
| Nominal output current | 8 A |
| Contacts type and composition | 1 C/O |
| Contacts material | Cadmium free |
| Height | 90 mm |
| Depth | 72 mm |
| control type | Selector switch front panel |
| [Us] rated supply voltage | 24…240 V AC 50/60 Hz 24 V DC |
| Voltage range | 0.85…1.1 Us |
| supply frequency | 50…60 Hz +/- 5 % |
| release of input voltage | 10 V |
| connections – terminals | Screw terminals, 1 x 0.5…1 x 3.3 mm² (AWG 20…AWG 12) solid without cable end Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 14) flexible with cable end Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end |
| tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Self-extinguishing |
| repeat accuracy | +/- 0.5 % conforming to IEC 61812-1 |
| Temperature drift | +/- 0.05 %/°C |
| Voltage drift | +/- 0.2 %/V |
| setting accuracy of time delay | +/- 10 % of full scale at 25 °C conforming to IEC 61812-1 |
| control signal pulse width | 100 ms with load in parallel typical 30 ms typical |
| insulation resistance | 100 MOhm at 500 V DC conforming to IEC 60664-1 |
| reset time | 120 ms on de-energisation typical |
| On-load factor | 100 % |
| power consumption in VA | 0…32 VA at 240 V AC |
| maximum power consumption in W | 0.6 W at 24 V DC |
| minimum switching current | 10 mA at 5 V DC |
| maximum switching current | 8 A AC/DC |
| maximum switching voltage | 250 V AC |
| Breaking capacity | 2000 VA |
| operating frequency | 10 Hz |
| electrical durability | 100000 cycles (8 A at 250 V AC maximum) for resistive load |
| Mechanical durability | 10000000 cycles |
| dielectric strength | 2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1 |
| [Uimp] rated impulse withstand voltage | 5 kV during 1.2/50 µs |
| power on delay | 100 ms |
| Marking of Schneider time relay RE17RCMU | CE |
| creepage distance | 4 kV/3 conforming to IEC 60664-1 |
| Safety reliability data | B10d = 270000 MTTFd = 296.8 years |
| mounting position | Any position in relation to normal vertical mounting plane |
| mounting support | 35 mm DIN rail conforming to EN/IEC 60715 |
| local signalling of Schneider time relay RE17RCMU | LED indicator for on steady: relay energised, no timing in progress LED indicator for flashing: timing in progress 80 % ON and 20 % OFF LED indicator for pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) 5 % ON and 95 % OFF |
| Product weight of Schneider time relay RE17RCMU | 0.07 kg |
| Time delay type of Schneider time relay RE17RCMU | C |
| Functionality of Schneider time relay RE17RCMU | Off-delay timing |
| Compatibility code | RE17 |
| Immunity to microbreaks | 20 ms |
| Standards of Schneider time relay RE17RCMU | EN 61000-6-4 EN 61000-6-2 EN 61000-6-3 2004/108/EC 2006/95/EC IEC 61812-1 EN 61000-6-1 |
| Product certifications | CULus GL CSA |
| Ambient air temperature for storage | -30…60 °C |
| Ambient air temperature for operation | -20…60 °C |
| IP degree of protection | IP20 (terminal block) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529 |
| vibration resistance of Schneider time relay RE17RCMU | 20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6 |
| shock resistance of Schneider time relay RE17RCMU | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| relative humidity of Schneider time relay RE17RCMU | 93 % without condensation conforming to IEC 60068-2-30 |
| electromagnetic compatibility | Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2 Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5 Conducted RF disturbances: (0.15…80 MHz), level 3, 10 V, conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11 Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11 Conducted and radiated emissions: , class B, conforming to EN 55022 |


0.0 Average Rating Rated (0 Reviews)