More items from this sellerView All

Schneider original circuit breaker MT40H1MIC2.0 2.0A 3P4p fixed drawer type

0 reviews

Schneider original circuit breaker MT40H1MIC2.0 2.0A 3P4p fixed drawer type Schneider Frame Breakers Model Number: MT40H1 . Schneider original circuit breaker

Description

PRODUCT INFORMATION OF SCHNEIDER  original circuit breaker MT40H1MIC2.0 2.0A 3P4p fixed drawer type

 

main information

Product Series MasterPact NW
product type Ontology
product short name MasterPact NW40
circuit breaker name MasterPact NW40H1
number of poles 4P
neutral position Left side
Network Type AC
Circuit breaker model H1
isolation function Applies to IEC 60947-2
use category Category B
Network frequency 50/60Hz
control type (Push) button
installation type Drawer
Rated current [In] 4000 A at 40 °C
Rated insulation voltage [Ui] 1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage [Uimp] 12 kV according to IEC 60947-2
Closure capacity [Icm] 143 kA 525 V AC at 50/60 Hz at
143 kA 690 V AC at 50/60 Hz at
Rated working voltage [Ue] 690 V AC 50/60 Hz conforming to IEC 60947-2
Transformer rating 4000A
Breaking capacity 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming IEC 60947-2
65 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
Use breaking capacity [Ics] 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
protection type Unprotected
Mechanical life 10000 times without maintenance according to IEC 60947-2
20000 times with maintenance according to IEC 60947-2
Electrical life AC-3: 6000 cycles of 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
2500 cycles of 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
5000 cycles of 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 2500 cycles of 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 5000 cycles of 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Phase spacing 150 mm
Rated short-time withstand current [Icw] 65 kA 1 s conforming to IEC 60947-2
65 kA 3 s conforming to IEC 60947-2
breaking time 25ms
Maximum closing response time 70ms
high of Schneider original circuit breaker 439mm
width of Schneider original circuit breaker 556 mm
depth of Schneider original circuit breaker 394.5 mm
Standards compliant IEC 60947-2
certified product ASTA
pollution level 4 Conforms to IEC 60664-1
operating temperature -25…70°C
storage environment temperature -40…85°C
Warranty of Schneider original circuit breaker 18 months