Description
| range of product | Altistart 22 |
|---|---|
| product or component type | Soft starter |
| product destination | Asynchronous motors |
| product specific application | Pumps and fans |
| component name | ATS22 |
| network number of phases | 3 phases |
| [Us] rated supply voltage | 230…440 V – 15…10 % |
| motor power kW | 110 kW 400 V 110 kW 440 V 55 kW 230 V |
| factory setting current | 195 A |
| power dissipation in W | 117 W for standard applications |
| utilisation category | AC-53A |
| type of start | Start with torque control (current limited to 3.5 In) |
| IcL starter rating | 210 A for connection in the motor supply line for standard applications |
| IP degree of protection | IP00 |
| assembly style | With heat sink |
| function available | Internal bypass |
| supply voltage limits | 195…484 V |
| supply frequency | 50…60 Hz – 10…10 % |
| network frequency | 45…66 Hz |
| device connection | To the motor delta terminals In the motor supply line |
| [Uc] control circuit voltage | 230 V – 15…10 % 50/60 Hz |
| control circuit consumption | 20 W |
| discrete output number | 2 |
| discrete output type | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
| minimum switching current | 100 mA at 12 V DC (relay outputs) |
| maximum switching current | 5 A 250 V AC resistive 1 relay outputs 5 A 30 V DC resistive 1 relay outputs 2 A 250 V AC inductive 0.4 20 ms relay outputs 2 A 30 V DC inductive 7 ms relay outputs |
| discrete input number | 3 |
| discrete input type | (LI1, LI2, LI3) logic, 5 mA 4.3 kOhm |
| discrete input voltage | 24 V <= 30 V |
| discrete input logic | Positive logic LI1, LI2, LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA |
| output current | 0.4…1 Icl adjustable |
| PTC probe input | 750 Ohm |
| communication port protocol | Modbus |
| connector type | 1 RJ45 |
| communication data link | Serial |
| physical interface | RS485 multidrop |
| transmission rate | 4800, 9600 or 19200 bps |
| installed device | 31 |
| protection type | Phase failure: line Thermal protection: motor Thermal protection: starter |
| Marking | CE |
| type of cooling | Forced convection |
| operating position | Vertical +/- 10 degree |
| Height | 425 mm |
| width | 206 mm |
| Depth | 299 mm |
| Net weight | 33 kg |
| Motor power range AC-3 | 55…100 kW at 200…240 V 3 phases 110…220 kW at 380…440 V 3 phases |
| motor starter type | Soft starter |
| electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-12 Electrostatic discharge level 3 conforming to IEC 61000-4-2 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Voltage/current impulse level 3 conforming to IEC 61000-4-5 |
| Standards | EN/IEC 60947-4-2 |
| product certifications | CCC UL GOST CSA C-Tick |
| vibration resistance | 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm (f= 2…13 Hz) conforming to EN/IEC 60068-2-6 |
| shock resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
| noise level | 56 dB |
| pollution degree | Level 2 conforming to IEC 60664-1 |
| relative humidity | 0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 |
| ambient air temperature for operation | -10…40 °C (without derating) 40…60 °C (with current derating 2.2 % per °C) |
| Ambient air temperature for storage | -25…70 °C |
| operating altitude | <= 1000 m without derating > 1000…< 2000 m with current derating of 2.2 % per additional 100 m |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 46.0 cm |
| Package 1 Width | 40.0 cm |
| Package 1 Length | 60.0 cm |
| Package 1 Weight | 24.5 kg |
| Warranty | 18 months |


0.0 Average Rating Rated (0 Reviews)