This Altivar 212 variable speed drive can feed 3-phase asynchronous motors.
Its protection index is IP21 and it has a built-in EMC filter.
It works at a rated power up to 2.2kW / 3hp and a rated voltage from 380V to 480V AC. Its design is based on eco-energy with a reduction in energy consumption of up to 70% compared to a conventional control system.
Thanks to its cable temperature rise reduction technology, the Altivar 212 drive offers immediate, disturbance-free operation avoiding additional options such as a line choke or DC choke to deal with current harmonics.
It weighs 2kg and its dimensions are, 107mm wide, 143mm high, 150mm deep. It is specifically designed for the most common fluid management applications in tertiary sector buildings (HVAC) like heating, ventilation, air conditioning and pumping.
It conforms to international standards IEC/EN 61800-5-1 and IEC/EN 61800-3 (immunity and conducted and radiated EMC emissions).
It is also CE, UL, CSA, C-Tick and NOM certified. The Altivar 212 offers optional motor chokes which can increase the maximum cable lengths between the drive and the motor and limit disturbance at the motor terminals.
It is designed to be mounted in vertical position (+/- 10 °) on a panel, thanks to 4 fixing holes. It can also be mounted directly on a 35 mm wide DIN rail, thanks to the kit VW3A31852, to order separately.
The Altivar 212 drive can easily be adapted to all building management systems thanks to its numerous functions and communication protocols integrated as standard, Modbus, METASYS N2, APOGEE FLN P1 and BACnet.
It is eco-friendly and complies with directives such as RoHS, WEEE, etc.relating to environmental protection.
PRODUCT INFORMATION OF SCHNEIDER ATV212HU22N4 inverter, 2.2kw ATV212 spot free shipping
Main
Device short name
ATV212
Product destination
Asynchronous motors
Network number of phases
3 phases
motor power kW
2.2 kW
motor power hp
3 hp
Supply voltage limits
323…528 V
supply frequency
50…60 Hz – 5…5 %
line current of ATV212HU22N4 inverter
3.6 A at 480 V
4.6 A at 380 V
Range of product
Altivar 212
Product or component type
Variable speed drive
Product specific application
Pumps and fans in HVAC
Communication port protocol
BACnet
LonWorks
Modbus
METASYS N2
APOGEE FLN
[Us] rated supply voltage
380…480 V – 15…10 %
EMC filter of ATV212HU22N4 inverter
Class C2 EMC filter integrated
IP degree of protection
IP21
apparent power
3.9 kVA at 380 V
continuous output current
5.1 A at 380 V
5.1 A at 460 V
maximum transient current
5.6 A for 60 s
Speed drive output frequency
0.5…200 Hz
speed range
1…10
speed accuracy
+/- 10 % of nominal slip 0.2 Tn to Tn
local signalling
1 LED (red) for DC bus energized
Output voltage
<= power supply voltage
Isolation of ATV212HU22N4 inverter
Electrical between power and control
type of cable of ATV212HU22N4 inverter
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection
sampling duration
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
response time of ATV212HU22N4 inverter
FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
accuracy of ATV212HU22N4 inverter
+/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °C
linearity error of ATV212HU22N4 inverter
VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for output
analogue output type
FM switch-configurable voltage 0…10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0…20 mA, impedance: 970 Ohm, resolution 10 bits
5 A at 250 V AC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load – cos phi = 1 – L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load – cos phi = 0.4 – L/R = 7 ms (FL, R)
discrete input type
F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
discrete input logic
Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
dielectric strength
3535 V DC between earth and power terminals
5092 V DC between control and power terminals
insulation resistance
>= 1 mOhm 500 V DC for 1 minute
frequency resolution
Display unit: 0.1 Hz
Analog input: 0.024/50 Hz
Communication service
Write single register (06)
Read device identification (43)
Time out setting from 0.1 to 100 s
Read holding registers (03) 2 words maximum
Write multiple registers (16) 2 words maximum
Monitoring inhibitable
option card
Communication card for LonWorks
Power dissipation in W
103 W
Air flow
35 m3/h
Functionality
Mid
Specific application
HVAC
Variable speed drive application selection
Building – HVAC Compressor for scroll
Building – HVAC Fan
Building – HVAC Pump
Motor power range AC-3
2.2…3 kW at 380…440 V 3 phases
2.2…3 kW at 480…500 V 3 phases
Motor starter type
Variable speed drive
Discrete output number
2
Analogue input number
2
analogue input type
VIA switch-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0…6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 10 bits
Analogue output number
1
Physical interface
2-wire RS 485
Connector type
1 open style
1 RJ45
Transmission rate
9600 bps or 19200 bps
Transmission frame
RTU
Number of addresses
1…247
Data format
8 bits, 1 stop, odd even or no configurable parity
Type of polarization
No impedance
Asynchronous motor control profile
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Voltage/frequency ratio, 5 points
Flux vector control without sensor, standard
Voltage/frequency ratio – Energy Saving, quadratic U/f
Voltage/frequency ratio, 2 points
Torque accuracy
+/- 15 %
transient overtorque
120 % of nominal motor torque +/- 10 % for 60 s
Acceleration and deceleration ramps
Automatic based on the load
Linear adjustable separately from 0.01 to 3200 s
Motor slip compensation
Not available in voltage/frequency ratio motor control
Adjustable
Automatic whatever the load
switching frequency
6…16 kHz adjustable
12…16 kHz with derating factor
Nominal switching frequency
12 kHz
Braking to standstill
By DC injection
Network frequency
47.5…63 Hz
Prospective line Isc
5 kA
protection type of ATV212HU22N4 inverter
Overheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motor
Width of ATV212HU22N4 inverter
107 mm
Height of ATV212HU22N4 inverter
143 mm
Depth of ATV212HU22N4 inverter
150 mm
Product weight
2 kg
pollution degree
3 conforming to IEC 61800-5-1
IP degree of protection
IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1
IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP21 conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
vibration resistance
1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8
shock resistance of ATV212HU22N4 inverter
15 gn for 11 ms conforming to IEC 60068-2-27
environmental characteristic
Classes 3C1 conforming to IEC 60721-3-3
Classes 3S2 conforming to IEC 60721-3-3
noise level of ATV212HU22N4 inverter
51 dB conforming to 86/188/EEC
operating altitude
1000…3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
<= 1000 m without derating
relative humidity
5…95 % without condensation conforming to IEC 60068-2-3
5…95 % without dripping water conforming to IEC 60068-2-3
ambient air temperature for operation
-10…40 °C (without derating)
40…50 °C (with derating factor)
Operating position
Vertical +/- 10 degree
Product certifications
CSA
NOM 117
UL
C-Tick
Marking of ATV212HU22N4 inverter
CE
Standards of ATV212HU22N4 inverter
IEC 61800-3
EN 61800-5-1
IEC 61800-3 environments 1 category C2
EN 61800-3 environments 1 category C2
EN 61800-3
EN 61800-3 environments 2 category C3
EN 61800-3 environments 1 category C1
IEC 61800-3 environments 1 category C3
IEC 61800-3 category C3
IEC 61800-3 environments 2 category C1
UL Type 1
EN 61800-3 category C3
EN 61800-3 environments 1 category C3
EN 61800-3 category C2
EN 61800-3 environments 2 category C2
IEC 61800-3 environments 2 category C3
EN 55011 class A group 1
IEC 61800-3 environments 2 category C2
EN 61800-3 environments 2 category C1
IEC 61800-5-1
IEC 61800-3 category C2
IEC 61800-3 environments 1 category C1
Assembly style of ATV212HU22N4 inverter
With heat sink
electromagnetic compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11