Description
PRODUCT INFORMATION OF Schneider ATV312HU22M2 inverter, ATV312 series 2.2kW single-phase spot
| range of product | Altivar 312 |
|---|---|
| product or component type | Variable speed drive |
| product destination | Asynchronous motors |
| product specific application | Simple machine |
| assembly style | With heat sink |
| component name | ATV312 |
| motor power kW | 2.2 kW |
| motor power hp | 3 hp |
| [Us] rated supply voltage | 200…240 V – 15…10 % |
| supply frequency | 50…60 Hz – 5…5 % |
| network number of phases | Single phase |
| line current | 21.9 A at 200 V, Isc = 1 kA 18.4 A at 240 V |
| EMC filter of ATV312HU22M2 | Integrated |
| apparent power | 4.4 kVA |
| maximum transient current | 16.5 A for 60 s |
| power dissipation in W | 123 W at nominal load |
| speed range | 1…50 |
| asynchronous motor control profile | Sensorless flux vector control with PWM type motor control signal Factory set : constant torque |
| electrical connection | Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1…LI6 terminal 2.5 mm² AWG 14 L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 5 mm² AWG 10 |
| supply of ATV312HU22M2 | Internal supply for logic inputs: 19…30 V 100 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (2.2 to 10 kOhm): 10…10.8 V 10 mA, protection type: overload and short-circuit protection |
| communication port protocol | CANopen Modbus |
| IP degree of protection | IP20 on upper part without cover plate IP21 on connection terminals IP31 on upper part IP41 on upper part |
| option card of ATV312HU22M2 | Communication card for CANopen daisy chain Communication card for DeviceNet Communication card for Fipio Communication card for Modbus TCP Communication card for Profibus DP |
| supply voltage limits | 170…264 V |
| prospective line Isc | 1 kA |
| continuous output current | 11 A at 4 kHz |
| Output frequency | 0…500 Hz |
| nominal switching frequency | 4 kHz |
| switching frequency | 2…16 kHz adjustable |
| transient overtorque | 170…200 % of nominal motor torque |
| braking torque | 150 % during 60 s with braking resistor 100 % with braking resistor continuously 150 % without braking resistor |
| regulation loop | Frequency PI regulator |
| motor slip compensation | Suppressable Automatic whatever the load Adjustable |
| output voltage | <= power supply voltage |
| tightening torque | Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1…LI6: 0.6 N.m L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-: 1.2 N.m |
| insulation | Electrical between power and control |
| analogue input number | 3 |
| analogue input type | AI1 configurable voltage 0…10 V, input voltage 30 V max, impedance: 30000 Ohm AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance: 30000 Ohm AI3 configurable current 0…20 mA, impedance: 250 Ohm |
| sampling duration | AI1, AI2, AI3: 8 ms analog LI1…LI6: 4 ms discrete |
| response time of ATV312HU22M2 | AOV, AOC 8 ms for analog R1A, R1B, R1C, R2A, R2B 8 ms for discrete |
| linearity error | +/- 0.2 % for output |
| analogue output number | 1 |
| analogue output type | AOC configurable current: 0…20 mA, impedance: 800 Ohm, resolution: 8 bits AOV configurable voltage: 0…10 V, impedance: 470 Ohm, resolution: 8 bits |
| discrete input logic | Logic input not wired (LI1…LI4), < 13 V (state 1) Negative logic (source) (LI1…LI6), > 19 V (state 0) Positive logic (source) (LI1…LI6), < 5 V (state 0), > 11 V (state 1) |
| discrete output number | 2 |
| discrete output type | Configurable relay logic: (R1A, R1B, R1C) 1 NO + 1 NC – 100000 cycles Configurable relay logic: (R2A, R2B) NC – 100000 cycles |
| minimum switching current | R1-R2 10 mA at 5 V DC |
| maximum switching current | R1-R2: 2 A at 250 V AC inductive load, cos phi = 0.4 and L/R = 7 ms R1-R2: 2 A at 30 V DC inductive load, cos phi = 0.4 and L/R = 7 ms R1-R2: 5 A at 250 V AC resistive load, cos phi = 1 and L/R = 0 ms R1-R2: 5 A at 30 V DC resistive load, cos phi = 1 and L/R = 0 ms |
| discrete input number | 6 |
| discrete input type | (LI1…LI6) programmable at 24 V, 0…100 mA for PLC, impedance: 3500 Ohm |
| acceleration and deceleration ramps | Linear adjustable separately from 0.1 to 999.9 s S, U or customized |
| braking to standstill | By DC injection |
| protection type | Input phase breaks: drive Line supply overvoltage and undervoltage safety circuits: drive Line supply phase loss safety function, for three phases supply: drive Motor phase breaks: drive Overcurrent between output phases and earth (on power up only): drive Overheating protection: drive Short-circuit between motor phases: drive Thermal protection: motor |
| insulation resistance | >= 500 mOhm 500 V DC for 1 minute |
| local signalling | 1 LED (red) for drive voltage Four 7-segment display units for CANopen bus status |
| time constant | 5 ms for reference change |
| frequency resolution | Analog input: 0.1…100 Hz Display unit: 0.1 Hz |
| connector type | 1 RJ45 for Modbus/CANopen |
| physical interface | RS485 multidrop serial link |
| transmission frame | RTU |
| transmission rate | 10, 20, 50, 125, 250, 500 kbps or 1 Mbps for CANopen 4800, 9600 or 19200 bps for Modbus |
| number of addresses | 1…127 for CANopen 1…247 for Modbus |
| number of drive | 127 for CANopen 31 for Modbus |
| marking of ATV312HU22M2 | CE |
| operating position | Vertical +/- 10 degree |
| outer dimension | 184 x 140 x 150 mm 230 x 200 x 152 mm 215 x 185 x 158 mm |
| height of ATV312HU22M2 | 184 mm |
| width of ATV312HU22M2 | 142 mm |
| depth of ATV312HU22M2 | 152 mm |
| net weight of ATV312HU22M2 | 3.1 kg |
| dielectric strength | 2040 V DC between earth and power terminals 2880 V AC between control and power terminals |
| electromagnetic compatibility | 1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 |
| standards of ATV312HU22M2 | IEC 61800-3 IEC 61800-5-1 |
| product certifications | NOM CSA DNV UL GOST C-Tick |
| pollution degree | 2 |
| protective treatment | TC |
| vibration resistance | 1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6 1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6 |
| shock resistance of ATV312HU22M2 | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
| relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 5…95 % without dripping water conforming to IEC 60068-2-3 |
| ambient air temperature for storage | -25…70 °C |
| ambient air temperature for operation | -10…50 °C without derating (with protective cover on top of the drive) -10…60 °C with derating factor (without protective cover on top of the drive) |
| operating altitude of ATV312HU22M2 | <= 1000 m without derating 1000…2000 m with current derating 1 % per 100 m |