Description
PRODUCT INFORMATION OF SCHNEIDER LV433485
Range | ComPact |
---|---|
Product name | ComPact NSX |
Range of product | ComPact NSX100…250 |
Device short name | NSX250HB1 |
Product or component type | Circuit breaker |
Device application | Distribution |
Number of poles | 4P |
Protected poles description | 4t |
Neutral position | Left |
[In] rated current | 250 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
Network type | AC |
Network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
Utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level | HB1 75 kA 690 V AC |
Trip unit name | TM-D |
Trip unit technology | Thermal-magnetic |
Trip unit protection functions | LI |
Control type | Toggle |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 8 kV |
[Ics] rated service short-circuit breaking capacity | 85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability | 20000 cycles |
electrical durability | 5000 cycles at 690 V In 10000 cycles at 690 V In/2 10000 cycles at 440 V In 20000 cycles at 440 V In/2 |
Mounting support | Backplate |
Upside connection | Front |
Downside connection | Front |
connection pitch | 35 mm |
protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
trip unit rating | 250 A at 40 °C |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
[Ir] long-time protection pick-up adjustment range | 0.7…1 x In |
Long-time protection delay adjustment type tr | Fixed |
[tr] long-time protection delay adjustment range | 120…400 s at 1.5 x In 15 s at 6 x Ir |
Short-time protection pick-up adjustment type Isd | Adjustable |
[Isd] Short-time protection pick-up adjustment range | 5…10 x In |
Short-time protection delay adjustment type tsd | Fixed |
Earth-leakage protection | Without |
Neutral protection settings | 1 x Ir (4t) |
Number of slots for electrical auxiliaries | 5 slot(s) |
Width (W) of Schneider LV433485 | 140 mm |
Height (H) of Schneider LV433485 | 161 mm |
Depth (D) of Schneider LV433485 | 86 mm |
Product weight | 2.8 kg |
Standards of Schneider LV433485 | EN/IEC 60947 |
Product certifications | Marine EAC CCC |
Overvoltage category | Class II |
Electrical shock protection class | Class II |
pollution degree | 3 conforming to IEC 60664-1 |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -50…85 °C |
relative humidity | 0…95 % |
operating altitude | 0…2000 m without derating 2000 m…5000 m with derating |
Warranty of Schneider LV433485 | 18 months |
0.0 Average Rating Rated (0 Reviews)