Description
PRODUCT INFORMATION OF YASKAWA GA800 Drive
|
Item
|
Specification
|
|---|---|
| Overload Capacity | 150% for 60 sec. (HD), 110% for 60 sec. (ND) |
| Output Frequency | 0~590 Hz |
| Control Methods | Open and Closed Loop Current Vector; Open and Closed Loop V/f |
| Motor Types | Induction Surface Permanent Magnet Interior Permanent Magnet Synchronous Reluctance |
| Protective Design | IP20 (IP20/UL Type 1 kit available) Flange (IP55/UL Type 12 backside) |
| Protective Design and Ambient Operating Temperature |
IP20/Protected Chassis(-10 to +50°C) IP20 with UL Type 1 kit (-10 to +40°C) Flange: front = IP20/Protected Chassis(-10 to +50°C); back = IP55/UL Type12 (-10 to +40°C) All types (additional +10°C with derate) |
| Global Certification | UL, CSA, CE, RCM, RoHS |
| Functional Safety | Safe Torque Off, SIL3 according to IEC 62061, PLe according to ISO 13849-1 (600V models pending, consult factory) |
| Standard I/O | (8) multi-function digital inputs (24Vdc) (3) multi-function analog inputs (0 +/- 10 VDC, 4-20 mA) (1) multi-function pulse inputs (2) Safe Torque Off inputs (1) fault relay output (form C) (3) multi-function relay outputs (form A) (2) multi-function analog output (0 +/- 10 VDC, 4-20mA) (1) multi-function pulse output |
| I/O Expansion | (3) Analog Inputs -10 to +10V, 13 bit plus sign, 4 to 20mA (16) Digital Inputs (2) Analog Outputs (-10 to +10V, 11 bit magnitude) (8) Digital Outputs (6 transistor, 2 relay) |
| Feedback | Incremental Absolute (Stegmann, Heidenhain, Resolver) |
| Network Communication | Standard: Modbus RTU, RS-485, 115 kbps
Optional: EtherNet/IP, DeviceNet, Modbus TCP/IP, PROFINET, PROFIBUS-DP |
| Speed Control Range | 1500:1 Closed Loop Vector (IM and PM Motors) 200:1 Open Loop Vector (IM Motors) 100:1 Open Loop Vector (PM Motors) |
| Speed Control Accuracy | ≤ 0.02%: Closed Loop Vector; ≤ 0.2%; Open Loop Vector |
| Speed Response | ≥ 50 Hz: Closed Loop Vector (Induction Motors) ≥ 250 Hz: Closed Loop Vector (PM Motors) ≥ 20 Hz: Open Loop Vector (Induction Motors) ≥ 40 Hz: Open Loop Vector (PM Motors) |
| Function Block Diagrams | Up to 200 connections, 500us program scan time |


0.0 Average Rating Rated (0 Reviews)