| Input, current |
Yes |
| Input, voltage |
Yes |
| Input, resistor |
No |
| Input, resistance thermometer |
No |
| Input, thermocouple |
No |
| Input signal, configurable |
Yes |
| Output, current |
No |
| Output, voltage |
No |
| Output signal configurable |
No |
| Analogue inputs configurable |
Yes |
| Analogue outputs configurable |
No |
| Type of electric connection |
Screw-/spring clamp connection |
| Local CJC sensor accuracy |
-3 to 3 °C |
| Channel bandwidth |
Notch Filter configuration dependent |
| Remote CJC sensor accuracy |
-3 to 4 °C |
| RTD excitation current |
600 μA |
| Module keying |
Electronic, software configurable |
| Module error over full temperature range |
0.1 % |
| Module conversion method |
Sigma-Delta |
| Input range |
1…500 ohm, 2…1000 ohm, 4…2000 ohm, 8…4000 ohm, -100…100 mV |
| Data format |
IEEE 32-bit floating point |
| Wire category |
2 – on signal ports |
| Overvoltage protection |
±30V DC maximum |
| Common mode noise rejection |
125 dB @ 60 Hz 1000 Ω differential, 120 dB @ 50 Hz 1000 Ω differential, 160 dB @ 600V 100 Ω differential |
| Normal mode noise rejection |
75 dB at 60 Hz |
| Module input scan time, min |
1 ms |
| Voltage and current ratings |
Backplane: 5.1V DC, 200 mA, 24V DC, 150 mA, Input: 1-4000 Ohms, +/-100mV, Thermocouple, B,C,E,J,K,R,S,T,N,D,L |
| Settling time |
Notch Filter configuration dependent |
| Total backplane power |
4.6 W |
| Thermal dissipation |
15.7 BTU/h |
| Current draw |
200 mA @ 5.1V, 150 mA @ 24V |
| Inputs |
Eight isolated channels – any combination of RTD or Thermocouple mode, Two CJC sensors for Thermocouple use. The CJC sensors, product catalog number 1756-CJC, do not come with the module. You must order the sensors separately. |
| Power dissipation |
4.6 W (15.7 BTU/hr) maximum |
| Resolution |
24 bit, 0…510 Ω: 0.06 mΩ/count, 0…1020 Ω: 0.12 mΩ/count, 0…2040 Ω: 0.25 mΩ/count, 0…4080 Ω: 0.50 mΩ/count, -101…101 mV: 0.01 μV/count |
| Wire size |
0.33…2.1 mm² (22…14 AWG) solid or stranded shielded copper wire, rated at 90 °C (194 °F) or greater, 1.2 mm (3/64 in.) insulation maximum |
| Calibrated accuracy |
0.05% @ 25 °C |
| Open circuit detection time |
Thermocouple input and 3-wire RTD input = 2 s, 4-wire RTD input = 5 s |
| Suitable for safety functions |
No |
| Thermocouple linearization |
ITS-90 |
| Thermocouple types |
B, C, D, E, J, K, N, R, S, T, TXK/XK L |
0.0 Average Rating Rated (0 Reviews)