Description
PRODUCT INFORMATION OF 1756-PA50 Rockwell AB Control Logix 10 communication module.
| Type of voltage (input voltage) | AC |
| Power output | 60 W |
| Output voltage at DC | 5.1 V |
| Input voltage, nom | 120/240V AC |
| Inrush current, max | 20 A |
| Input power, max | 81 W/91VA @ 50 °C (122 °F), 68 W/77VA @ 60 °C (140 °F) |
| Current capacity | 8 A @ 50 °C (122 °F) @ 5.1V DC, 6 A @ 60 °C (140 °F) @ 5.1V DC |
| Power output, max | 60 W @ 0…+50 °C (+32…+122 °F), 50 W @ 0…+60 °C (+32…+140 °F) |
| Wire category | 1 – on power ports |
| Hold-up time | 4 cycles @ 85…265V AC, 50/60 Hz, 60 W, 5 cycles @ 85…265V AC, 50/60 Hz, 50 W |
| Wire size | 2.5 mm² (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max |
| Suitable for safety functions | No |
| Type of output voltage | DC |
| Input voltage at AC 50 Hz | 85 V |
| Input voltage at AC 60 Hz | 85 V |
| Redundancy capable | No |
| Input frequency | 47 Hz |
| Width | 78 mm |
| Height | 140 mm |
| Depth | 145 mm |
| Enclosure type rating | None (open-style) |
| Weight | 0.77 kg |
| ISAGX | No |
| Rockwell tire and rubber rated | No |
| Conductor screw torque | 0.565 Nm |
| Vibration | 2 G @ 10…500 Hz |
| Relative humidity | 5…95% noncondensing |
| Shock | Operating: 30 G |
| Operating temperature | 0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F) |
| Voltage variation | IEC 61000-4-11: 30% dips for 1 period at 0° and 180° on AC supply ports, 60% dips for 5 and 50 periods on AC supply ports, ±10% fluctuations for 15 min on AC supply ports, >95% interruptions for 250 periods on AC supply ports |


0.0 Average Rating Rated (0 Reviews)